If the supply drops mid-run, a latching circuit stays off after restore and needs a fresh start press. This page explains why that is by design and safe.
The latch holds the coil through the KM NO auxiliary across the start. On control power loss the contactor drops and the auxiliary opens; when supply returns the auxiliary is already open and nobody is pressing start, so no path energizes the coil and the motor stays still. This is the natural no-auto-recovery of a latch, a form of under-voltage protection.
Auto-restart on return is a different, dedicated design and is forbidden for general machines by GB/T 5226.1, which requires manual reset after supply recovery. If your motor spins up on return, that is not normal latching but a fault: a stray self-hold, an NC button, or welded main contacts, to be checked per el-1119.
| Circuit | After loss | On return |
|---|---|---|
| Plain latch | drops | manual |
| Faulty | odd | auto risk |
| Need auto | add relay | auto |
| UV protect | no surge | safe |
| Std | no auto | manual |
| Check | el1119 | weld |
A plain latch will not auto-restart after a blackout; it needs a manual start, which is safe under-voltage behaviour. For loads that must resume, add a restart relay or PLC logic with sequencing; for faulty auto-start, inspect per el-1119.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machine safety GB/T 5226.1 with IEC 60204-1; contactor GB/T 14048. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.