Press the button and the motor does not move; usually the control loop is open. This page gives a control-first then power-loop troubleshooting routine.
First split the fault: measure across the coil while pressing. If coil voltage appears but the contactor will not pull in, the contactor itself is bad (stuck armature, open coil). If no voltage, the control loop is open (button, wiring, supply). Jog with no load to see if the contactor pulls in; if it does, the control is fine and the fault is in the main loop or mechanics.
Open points in control: oxidized or loose NO button, blown control fuse (often overlooked), loose terminal screws, a stop button left open or miswired, or wrong phase feed giving no voltage. Buzz from the supply end segment by segment. If the contactor pulls in but the motor stays still, check the main loop: tripped breaker, blown fuse, welded or poor main contacts, loose motor leads, tripped overload. A buzzing not fully pulled-in coil means low voltage or dirt on the core.
| Sign | Check | Fix |
|---|---|---|
| No coil V | button/fuse/term | trace through |
| V but no pull | contactor bad | replace |
| Pull no turn | main loop | breaker |
| Buzzing | low V / dirt | clean core |
| OL tripped | overload | reset |
| Jammed | load stuck | bar the load |
Do not swap parts blindly; check control loop then main then mechanics. Carry a buzzer meter and trace from the control supply; the break shows up fast. Most cases are loose buttons, blown control fuse or poor terminals.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Maintenance follows GB/T 5226.1 with IEC 60204-1; devices follow JIS C 4501. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.