Grounding shield layers through terminal blocks

A badly grounded shield is no shield at all: noise still leaks into the analogue loop. This page covers how to land the braid on the strip, single or both ends, clamping and marking.

1. How it works

After the shielded cable enters the cabinet, strip 15 to 20 mm of braid and clamp it in a metal shield-clamp terminal, never twist the braid into a pigtail and cram it into an ordinary terminal, which breaks strands and adds contact resistance. Shield terminals form a metal bar or join a dedicated bus, and the whole row lands at one point on the signal earth. Take care not to nick the core insulation and fit an insulating sleeve under the braid.

2. Practice and pitfalls

Single or both ends: low-frequency analogue and comms cables ground the shield at one end only, inside the cabinet on the strip, the far end heat-shrunk and floating to avoid ground loops carrying mains noise; high-frequency shields (encoder cable) may ground both ends. Drive output cable shields join both ends in a full 360-degree EMC clamp, not a thin pigtail. Keep one rule per cabinet and mark the earthing method of every shielded run on the drawing.

3. Shield earthing methods

CircuitEarthingPractice
AnalogueOne endCabinet SE, far end sealed
CommsOne endSame as analogue
EncoderBoth allowedBoth to SE
Drive out360 deg bothEMC clamp
Spare shieldSame ruleNot cut
MarkingSE tagGreen

4. Notes

Clamp braids in dedicated shield terminals landing on one point of the signal earth; never twist into ordinary terminals. Low-frequency and comms ground one end with the far end sealed, high-frequency may use both, drive outputs use 360-degree EMC clamps. Mark SE and measure braid-to-earth under 1 ohm to prove a true ground.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: EMC installation per GB/T 17799.2, marking per GB/T 4026, documents per GB/T 6988. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Twisted braid in ordinary terminal leaks noise
② Both-end ground on low frequency adds loop hum
③ Nicking core insulation shorts to earth

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.