A wire number is not alone; it must form one retrievable coding system with drawing numbers, device tags and terminal numbers. Here is how to design it as a whole.
A complete electrical code has three layers: the drawing number locates the sheet, the device tag or component designation locates the equipment, and the wire number locates the wire. They must index each other: the sheet number finds the drawing, the wire number on it points to a terminal, the terminal maps to a device tag. Set the naming rules early in the project and write them into the design spec, or later everyone draws their own and tracing breaks at every step.
The steps: fix the sheet rule (e.g. EL-01 schematic, EL-02 wiring), then device tags (M1 motor, KM1 contactor), then wire numbers (power from 101, control from 201). Example: on EL-02 terminal X1:3 carries wire 101 going to EL-03 page 202-5, device M1 terminal 101. Any wire is then traceable sheet to tag to number. Freeze the three-way mapping in a table.
| Layer | Code | Locates |
|---|---|---|
| Sheet | EL-01/02 | Which sheet |
| Device | M1/KM1 | Which equip |
| Wire | 101/201 | Which wire |
| Map | Three-way table | Cross index |
| Example | EL-02 X1:3 | 101 to M1 |
| Change | Sync three | No break |
Rule: three layers, sheet locates drawing, device tag locates equipment, wire number locates wire, all cross-indexed. Unify rules early, build the mapping table, sync all three on change, newcomers follow the spec; do not let each person code their own.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation and item codes per GB/T 6988 and GB/T 5094, graphical symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.