Interlock between main and delta contactors in star-delta

Wrong interlock among KM1, KM2 and KM3 in star-delta causes short or loss of control. This article explains the NC series logic between the main, delta and star contactors and the consequence of missing interlocks, with a table.

1. How it works

KM1 is the main supply contactor, held in continuously; KM2 is the delta contactor. A KM1 NC auxiliary is wired in series with the KM2 coil so KM2 cannot act before KM1 pulls in, preventing delta without star. KM2 NC also feeds back to lock later logic, forming a master-slave constraint that avoids conflict.

2. Numbers and practice

KM2 (delta) and KM3 (star) must never close together; if they do, the star point and delta bridge coexist as a phase-to-phase short. Wire KM2 NC in the KM3 coil and KM3 NC in the KM2 coil, interlocking both ways. Even if the KT contact fails, the interlock saves the circuit; it is the most critical safety link.

3. Pitfalls and fixes

If a contactor lacks enough auxiliary contacts, extend with an intermediate relay KA or choose a multi-contact type. Mechanical interlock built into the contactor can pair with the electrical one for double protection. Always prove with lamps that no two contactors can pull in together.

4. Star-delta contactor interlock table

PairWiringEffectFailure
KM1-KM2KM1 NC in KM2no direct deltafull-voltage start
KM2-KM3NC series bothno simultaneousphase short
KM3-KM2NC series bothno simultaneousphase short
Mech lockcontactor bodydoubleelectrical only risky
Extendadd KAenough contactsmissed lock

5. Notes

Rule: KM1 moves first, KM2 and KM3 must interlock, never omit. Verify each NC pair with lamps so no two pull in together; one missing link can short and explode the contactor, so commission slowly.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactors per IEC 60947-4-1, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Omit KM2-KM3 interlock and short.
② Rely on mechanical only, no electrical.
③ Skip contact extension when short.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.