Knowledge Base › Electrical Knowledge Base › Troubleshooting both devices starting together from interlock misoperation
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Troubleshooting both devices starting together from interlock misoperation

An interlock should keep two devices mutually exclusive, yet misoperation lets them start together, causing process chaos or collision. This article starts from four causes: contact welding, wrong wiring, voltage anomaly and interference, and gives location and troubleshooting steps.

1. How it works

Welded main or auxiliary contacts are the most common cause: a welded main contact keeps one device running, and a welded NC auxiliary cannot open the interlock so the opponent can close together. Troubleshoot by measuring contact resistance when open; a welded contact reads continuity. Replace the contactor and add mechanical interlock as redundancy to avoid single-point failure.

2. Practice and pitfalls

Miswiring the interlock as NO, omitted or paralleled disables it so both can start. Low or fluctuating control voltage makes the contactor release sluggishly and chatter, briefly closing both. Check contact type and series position point by point, measure the supply dip at start, and enlarge the control transformer or supply separately if needed.

3. Both-start troubleshooting

CauseSymptomAction
WeldedNo openReplace
Wrong wireInterlock lostFix per drawing
Low voltageChatter dualBigger supply
InterferenceIntermittentShield separate
ButtonWater ingressClean replace

4. Notes

Both-start faults mostly come from welded interlock contacts or wiring errors; troubleshoot by measuring resistance off-power, checking the drawing point by point, measuring start voltage and reproducing with the simultaneous-button test. Intermittent faults point to interference or poor contact, not just a reset.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear per GB 14048.4, EMC per GB/T 17626 series, referencing IEC 60947 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Welded NC auxiliary cannot open, both close
② Interlock as NO fails, both start
③ Voltage chatter causes brief dual close

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.