Knowledge Base › Electrical Knowledge Base › Troubleshooting lost self-hold from a bad latch contact
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Troubleshooting lost self-hold from a bad latch contact

The motor runs while the start is held then stops on release, meaning the latch never built. Usually the auxiliary contact is bad or missing. This page gives a step-by-step.

1. How it works

Typical sign: hold start, motor runs, release, it stops like jog. First confirm the start is NO and the stop NC is not stuck. If hold-runs release-stops, the fault is in the latch branch: the KM NO auxiliary is not closing, has high resistance, is loose, or was never paralleled across the start.

2. Practice and pitfalls

With power off measure the KM auxiliary NO: when the armature is in it should read near 0 ohm, open when out; if still open when in, the aux is bad or unwired. Temporarily short the two latch terminals; if it then holds, the aux or its wire is the fault. Check terminal tightness, confirm 13-14 or 21-22 is the NO not NC, and measure 0 V across it when pulled in.

3. Lost latch troubleshoot

SignCheckFix
Drops releaseaux statemeasure
Open when inaux badswap contactor
Short holdsaux faultfind wire
Loose termwire offre-tighten
Wrong contactother KMcorrect
NC by mislatches onuse NO

4. Notes

For lost self-hold inspect the auxiliary contact: it must close when pulled in and stay across the start. Measure, short-test and check terminals; confirm it is the NO contact wired to the right contactor. Verify hold on release after fix.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor per GB/T 14048 and IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Think coil bad: swap wastes money
② Aux wired NC: latches on power
③ Aux on wrong KM: no self-hold

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.