Wiring steps and contact mapping for forward-reverse circuits

One wrong step in a forward-reverse circuit means full rework; wiring by ordered steps with a contact mapping checklist gets it right the first time. This article walks through main circuit, stop branch, forward and reverse branches and interlock contacts, with a contact-by-contact mapping table.

1. How it works

Main circuit first: supply enters KM1 main contacts through breaker QF and fuses FU, KM1 outgoing lines go through the thermal elements of FR to motor terminals U, V and W. KM2 upper terminals parallel onto the same supply, but its lower terminals cross U and W before joining the FR input side, with phase V passing straight through. Keep the cross on the load side of the contactors, and meter all phases for shorts before touching the control circuit.

2. Practice and pitfalls

Control circuit next, starting from the 110 V or 220 V control supply: the stop button NC comes first, then splits into two branches. The forward branch is SB2 NO in series with the KM1 coil, with a KM1 NO auxiliary paralleled across SB2 for latching; the reverse branch mirrors it with SB3 and KM2. Interlock contacts go in last: KM1 NC into the KM2 coil branch and KM2 NC into the KM1 coil branch, plus crossed NC contacts when composite buttons are used. Verify every contact with a buzzer meter against the drawing before any power is applied.

3. Contact mapping table for forward-reverse wiring

ContactTypeLocationFunction
KM1 main contactsMainMain circuitForward connection
KM2 main contactsMainMain circuit, two phases crossedReverse connection
KM1 auxiliary NONOParallel across SB2Forward latch
KM2 auxiliary NONOParallel across SB3Reverse latch
KM1 auxiliary NCNCSeries in KM2 coil branchForward interlock
KM2 auxiliary NCNCSeries in KM1 coil branchReverse interlock
FR NC contactNCSeries in control supply pathOverload protection

4. Notes

Copy this table to the workbench and tick one line per contact. Composite button NC terminals belong on the list too; most rework hides there. Checklist plus buzzer meter is the cheapest error-proofing pair.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 and GB 14048.5 for low-voltage switchgear, GB/T 5226.1 for machinery safety, IEC 60947-5-1 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Cross on supply side: swap fails and shorts risk, cross only on the load side
② Latch wired where interlock belongs: erratic action, check point by point
③ FR in only two phases: protection lost, all three elements in series

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.