The interposing relay is the universal supporting actor of control circuits: it expands contacts, converts levels, forwards signals and holds states. This page gathers its four roles, four sizing checks and three canonical wirings in one place.
Four roles cover most needs. Contact expansion: a contactor offers two NO and two NC auxiliaries while interlocks, lamps, alarms and PLC signals need more, so wire the KA coil across the KM coil and its contact set acts in step, multiplying available points. Signal forwarding: cross-panel and cross-building signals go through a KA, avoiding the voltage drop and noise of long direct runs from contactor contacts. Level conversion: a 220V control state feeding a 24V PLC input uses a KA with a 220V coil and 24V contacts, keeping power and signal cleanly apart. State memory: latched KAs hold fault lockouts and cycle states until a deliberate, human-confirmed reset.
Four sizing checks: coil voltage matching the circuit with AC and DC never mixed; contact rating, trivial for lamps and PLC inputs but verified against pickup VA when driving a contactor, where 5~10A contacts comfortably carry small and medium coils; contact count with twenty percent headroom, preferring one multi-contact model over two paralleled units since paralleled contacts never close together and the first takes the full surge; and mechanical life of a hundred thousand operations or better for frequent duty. The KA coil is inductive, so contacts driving it need arc consideration and an RC snubber on critical duty, and coil open-circuit spikes of hundreds of volts demand suppression where electronics share the loop.
Three canonical wirings: state forwarding, KA1 across KM1 feeding lamps, downstream interlocks, alarms and the PLC from one relay; fault memory, parallel thermal alarm contacts fire KA2 which latches through a reset button, locking the start circuit until a human confirms; timer isolation, the latch contact forwards through KA3 into the KT so the timer sees one clean contact instead of the busy main rung. Commission each KA by hand-closing its armature and verifying every output circuit, then integrate; quarterly, measure contact resistance and clean or replace beyond 0.1 ohms.
| Use | Wiring | Sizing point | Note |
|---|---|---|---|
| Contact expansion | KA across the KM coil | Contact count plus 20% | Prefer multi-contact models |
| Signal forwarding | Cross-panel KA isolation | Rating per load | No long direct runs |
| Level conversion | HV coil, LV contacts | Separate AC and DC | Isolate power and signal |
| State memory | Latch plus reset button | 100k mechanical life | Human-confirmed release |
| Fault lockout | Thermal contacts fire KA | NO alarm contacts | Start circuit locked until reset |
| Timer drive | KA contact into KT | Keep KT off the main rung | Mind contact arcing |
Align use, wiring and sizing from this table at design and maintenance alike. A relay costing a dozen yuan buys layered logic: contactors handle power, KAs handle signals, and layered panels fail less and repair faster; building clear hierarchy from small parts is where electricians start becoming designers.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control relay requirements follow the GB/T 14598 series and GB/T 14048.5; control circuit design principles refer to GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.