High speed runs fine but low speed refuses, the signature two-speed motor fault. This page ranks six causes from most to least likely, from the shorting path through interlock deadlocks to winding and load issues, each with its verification method.
The low-speed delta requires U2V2W2 shorted, and that shorting path, made by KM3 contacts or links, accounts for over half of all low-speed no-start faults. Three variants: KM3 never picks up because its feed through a KM1 auxiliary contact is miswired or oxidized; KM3 picks up but its contacts are poor, leaving the short path resistive so the phase currents unbalance and the motor hums without turning; or the terminal links are fitted wrongly for the mode. Verify with the power off by measuring resistance across U2V2W2 with KM3 simulated closed, expecting fractions of an ohm; on power, current imbalance beyond thirty percent confirms the shorting problem.
The second family lives on KM1 and the interlock chain: KM1 main contacts badly eroded, dropping too much voltage under the heavy low-speed delta current so terminal voltage cannot produce starting torque; KM1 not picking up at all, where any open point in the button, interlock or thermal-relay chain kills the coil, found by probing voltages point by point; or an interlock deadlock, a welded KM2 normally-closed contact from a previous high-speed fault holding KM1 out, giving the on-and-off symptom that recovers after cooling. Always re-test hot, not just cold, for this family.
The third family sits in the machine and load: an open or shorted half-winding, since the delta needs both halves of each phase sound, detectable with a bridge comparison of the three phase resistances; a jammed or starved load, because low-speed torque is limited on constant-power windings, proven by uncoupling and running no-load; and operation-side breaks such as a broken low-speed button lead or a selector left off. The discipline: no-load before load, control before power, cold before hot, and the path never doubles back.
| Likely cause | Occurrence | Verification | Remedy |
|---|---|---|---|
| KM3 missing or poor contacts | About 50% | Short path below 0.5 ohms | Clean or replace KM3 |
| KM1 main contacts eroded | About 15% | Measure contact resistance | Dress or replace |
| Interlock welded deadlock | About 10% | Re-test interlock chain hot | Replace welded contact |
| Half-winding open or shorted | About 10% | Bridge the three phase resistances | Send for rewind |
| Jammed load | About 10% | Uncouple, run no-load | Fix mechanics and lubrication |
| Operation circuit break | About 5% | Probe button and selector | Restore wiring |
Follow the ranking and close the job at the first hit. Low-speed no-start looks complex but is mostly the shorting path: quarterly maintenance of KM3 contacts and link tightness removes eighty percent of these calls.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Safety requirements for fault diagnosis follow GB/T 5226.1; winding resistance measurement refers to GB/T 1032. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.