When simplified drawing methods are allowed on circuit diagrams

Drawing the same contactor seven times is tedious; simplified methods save effort but used wrongly they confuse the reader. This page tells which simplifications are allowed and when the full drawing is mandatory.

1. How it works

Common simplifications are of three kinds: a device appearing many times is drawn once with letter tags (e.g. auxiliary contacts of KM1 scattered but tagged KM1; a group of circuits enclosed by a chain-dotted line drawn only at ends; and a function box (e.g. a VFD as a rectangle with model and parameters instead of internal circuit). GB/T 4728 defines the graphics; they are not invented symbols. Simplification speeds reading, not omitting information.

2. Practice and pitfalls

Use simplification only for repeated standard units (e.g. identical soft-starter mains drawn as boxes), for multiple contacts of one device tagged with the same letter, and for complex internal boards shown as a box with pin numbers. Never simplify safety or e-stop circuits, which must show every contact, or the maintainer cannot see the real on/off state; training diagrams should also be full.

3. Simplified drawing conditions

MethodAllowedForbidden
Multi-pointTag same codeSafety circuit
Function boxRepeated unitUnique circuit
Chain lineGroupedWhere check needed
Board boxComplex insidePins must map
SafetyAlways fullNever skip

4. Notes

Simplify only repeated, standard and boxed complex parts; safety and e-stop circuits must show every contact. Tag the original model beside each simplified symbol and map box pins to the outer circuit one-to-one. Per GB/T 5226.1 safety contacts are never simplified.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Symbols per GB/T 4728, documents per GB/T 6988, safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Simplifying the e-stop into a box hides the real contact
② Scattered contacts tagged without index confuse same-model devices
③ Wrong box pin numbers mismatch field wiring

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.