Too small a terminal overheats and burns, too large wastes space. This page shows how to size terminal current rating by wire and load, plus key selection points.
Match the terminal rating to the conductor: 2.5 mm² with 6 A, 4 mm² with 16 A, 6 mm² with 32 A, 10 mm² with 57 A (per IEC 60947-7-1 current table. Use the terminal nameplate current, not just the wire, because the internal spring contact resistance sets heating. Rule: step the wire up one size, leave terminal margin, and keep load under 80 percent of rating. Trap: forcing 10 mm² into a 2.5 mm² terminal gives poor contact and arcing.
Correct for environment: stranded wire needs a crimp lug (OT) or it loosens; high temperature over 40 ℃ derates 20 to 30 percent; a full packed row also derates. Power loops use screw clamp against vibration, signal loops use spring type maintenance-free. Keep the sum of the row load within rail and cabinet cooling, add barriers or spare holes where dense. When ordering state wire size, current and vibration.
| Wire mm² | Term A | Use |
|---|---|---|
| 2.5 | 6 | Signal |
| 4 | 16 | Control |
| 6 | 32 | Small power |
| 10 | 57 | Power |
| 16 | 76 | Big power |
| 25 | 101 | Main |
Size terminal by wire cross-section (2.5 mm²/6 A, 10 mm²/57 A per IEC 60947-7-1) with load under 80 percent of rating. Derate 20 to 30 percent when hot, crimp stranded wire, use screw type for power. Avoid three errors: ignoring peak, mixing sections, skipping derating; always crimp lugs on power wire with 1.5x margin.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation per GB/T 6988, terminals per IEC 60947-7-1, assemblies per GB/T 7251.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.