A three-phase induction motor reverses when any two supply lines are swapped, flipping the rotating magnetic field. This article explains the essence of phase swapping, how two contactors cross-wire the main circuit, and how the control circuit uses interlocks to keep them from closing together.
The direction of a three-phase induction motor follows its rotating magnetic field, which depends on the phase sequence of the supply. Swapping any two of the three motor leads reverses the sequence and the rotation. In the main circuit two contactors do exactly this: KM1 feeds the motor in the order L1-L2-L3, while KM2 feeds it with two phases crossed, so its load-side lines land on different terminals. The third phase passes straight through and is never swapped, which keeps the wiring simple and easy to check.
The main circuit arrangement: supply goes through switch QS and fuses FU to KM1 main contacts, then through the thermal elements of FR to motor terminals U, V and W. KM2 sits in parallel after KM1 but crosses two of its outgoing phases, for example its L1 line lands on W and its L3 line on U. On the control side, each coil branch carries the NC auxiliary contact of the other contactor, plus push-button interlock with composite buttons, forming a double interlock so at most one contactor can be energized at any moment. A drawing without interlock must never be built as a real panel.
| Item | Supply side | Load side to motor | Result |
|---|---|---|---|
| KM1 | L1-L2-L3 in order | U-V-W | Forward |
| KM2 | L1-L2-L3 in order | W-V-U (two phases crossed) | Reverse |
| Phase V | Direct through | V | Common |
| Overload relay FR | After contactors | All three lines | Overload protection |
| Interlock contact | KM1 NC in KM2 coil | KM2 NC in KM1 coil | No simultaneous pull-in |
The whole idea fits in one line: swap two phases and add interlock. Check the crossed phases with a meter before the first start; a wrong cross turns both buttons into the same direction.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 755 and GB/T 5226.1 for motor control, GB 14048.4 for contactors, IEC 60204-1 and IEC 60947-4 for reference. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.