Terminal numbers detached from device tags force three trips through the drawings for one wire. This page shows how to carry the device tag inside the terminal number and build a two-way index.
The most direct link is to carry the device tag inside the terminal number: device tag plus terminal, e.g. KM1:A1, X1:12. On the strip drawing each hole shows its sequential number plus the connected device tag and device terminal, binding three codes (hole, tag, device terminal) on one sheet. EPLAN generates this map with functional texts and connection points; tracing by tag jumps straight to the hole instead of scanning the strip.
Build a two-way index: forward from terminal to device (X1:12 to KM1:A1) and backward from device to terminal (KA2:9 to X1:31). Archive it with the drawing and update on any change. The rule must be uniform across the cabinet, no strips with tags and others with bare sequence numbers. Multi-level terminals add a level letter such as X1:12B. Trap: one wrong letter (KA2 written as KA5) traces to the wrong relay.
| Hole no | Device tag | Device term |
|---|---|---|
| X1:1 | QF1 | 1 |
| X1:12 | KM1 | A1 |
| X1:31 | KA2 | 9 |
| X1:12B | KM1 | A2 |
| X2:5 | V1 | PE |
| X3:8 | SB1 | 2 |
Carry the device tag inside the terminal number and keep a two-way index so either end of a number leads to the other; keep the rule uniform and add level letters. Review hole by hole, spot-check 10 percent after wiring, laminate the index on the door, and change all three documents together.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Documents per GB/T 6988, terminal marking per GB/T 4026, tagging per IEC 81346. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.