Earth symbols: the different types and where each one belongs

There is more than one earth symbol, and protective, functional and equipotential earthing are drawn differently. This page explains the distinction between the earth symbols and which one fits which situation.

1. How it works

GB/T 4728 draws earthing as a vertical line with three short bars underneath, but the purpose changes the symbol: protective earth PE uses a bold or half-ring earth symbol for connection to the protective conductor; functional earth (signal ground) uses the thin symbol for the electrical reference point; equipotential bonding is a horizontal line with the earth symbol tying several enclosures to one potential; lightning protection carries its own mark. Drawing the wrong type makes the crew bond signal ground onto the protective bar and injects interference into analogue circuits.

2. Practice and pitfalls

Choose by system requirement: enclosures in a TN system take the PE symbol; the 0V reference of instruments and PLCs takes functional earth; machine rooms and workshops tie all metal enclosures with equipotential bonding; lightning protection gets its own electrode and symbol. Every earth on the drawing must show where it connects, and whether protective and signal earth share one point or stay separate must be declared, or a common path couples interference between the two.

3. Earth symbol types and applications table

Earth typeSymbol featureLetter codeApplication
Protective earthbold earth symbolPEenclosures to protective conductor
Functional earththin earth symbolFEinstrument reference point
Equipotential bondingline plus earth symbolEBbonding several enclosures
Lightning earthlightning mark addedLPSdown conductor system
Screen earthearth plus screen markSEcable shield layer

4. Notes

Protective, functional and equipotential earth symbols differ, and mixing them up bonds signal ground to the protective bar and imports interference. Declare where every earth lands, and measure the resistance after construction: protective earth generally not above 4 ohms, lightning earth not above 10 ohms.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Earth symbols per GB/T 4728.3; earthing systems per GB/T 16895 and IEC 60364 series. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Signal ground bonded to the protective bar: mains interference makes analogue values jump
② Equipotential bonding broken on the drawing: potential difference between enclosures fries communication ports
③ Lightning and protective earth mixed: surge current invades the control cabinet

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.