A contactor draws a big inrush to pull in but only a small current to hold. This page explains the relation and why it matters for latching.
An AC coil is inductive; at pick-up the air gap is large so reluctance is high and it needs a large current, about 6 to 10 times the hold current, to build the field and seat the armature. Once seated the gap is near zero, reluctance drops and only a small hold current keeps the field. DC coils use an economy resistor or dual winding to split pick-up and hold.
After the latch builds, the KM auxiliary bypasses the start and feeds the coil at hold current, low power and low heat. Size the control supply by hold current, not pick-up. Frequent jogging hammers the coil with inrush spikes and heats more than continuous run, so pick a high electrical-life or AC-4 contactor for jogging.
| Phase | Current | Note |
|---|---|---|
| Pick-up | 6-10x | build field |
| Hold | base | gap zero |
| DC | split | economy |
| Jog | repeated | heats |
| Supply | by hold | size |
| Overheat | el1116 | volt block |
Pick-up current far exceeds hold current; once latched the coil only draws hold current at low loss. Size control supply by hold current and choose high-life contactors for jogging. Coil overheating points to voltage or sticking, see el-1116.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor GB/T 14048.4 with IEC 60947-4-1; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.