How much current does an 11kW motor draw, and what flows in a contactor coil loop? Without current numbers, sizing and protection are guesswork. This page works both sides through concrete examples with formulas and results.
Rated current of a three-phase motor follows I = P/(1.732 x U x cosphi x efficiency). For 11kW at 380V with cosphi 0.85 and efficiency 0.9, I = 11000/(1.732 x 380 x 0.85 x 0.9) which is about 21.8A; the shop rule of roughly 2A per kW gives 22A and confirms it. Feeder current for several motors sums the loads times a diversity factor of 0.7 to 0.9. From there set the breaker at 1.05 to 1.1 times rated current and the thermal relay at 0.95 to 1.05 times.
Control current has two parts: holding and pull-in. An AC110V auxiliary relay holds at about 0.03A (a few watts) and pulls in at 5 to 10 times that, around 0.2A; a large-frame contactor on AC220V holds at 0.1 to 0.5A with a several-fold inrush. Transformer sizing multiplies the sum of simultaneous holding powers by 1.5 to 2: six 3W relays plus two 20VA contactors at 0.8 diversity is roughly 40VA, and a 250VA unit leaves generous margin on top of lamps and PLC loads.
Verify three things after calculating: conductor ampacity at least 1.2 times the computed current; secondary fusing at 1.5 to 2 times loop rating so pull-in shocks do not melt the fuse; and any measured deviation above 10 percent from calculated current deserves investigation rather than a quiet adjustment of settings. Do the arithmetic twice, once by formula and once mentally; a gap over 10 percent means a copied parameter.
| Item | Formula | Result | Used for |
|---|---|---|---|
| 11kW motor rated current | 11000/(1.732x380x0.85x0.9) | About 21.8A | Breaker and cable sizing |
| Feeder composite current | (11+5.5+2.2)kW x 2A x 0.8 | About 30A | Common feeder sizing |
| Contactor coil holding | 20VA/220V | About 0.09A | Transformer VA budget |
| Relay pull-in current | 0.03A x 8 | About 0.24A | Fuse withstand check |
| Transformer capacity | (6x3+2x20)VA x 0.8 x 1.5 | About 62VA | 250VA fitted with margin |
| Secondary fuse | Loop current x 1.5 to 2 | Rounded to size | Ride through inrush |
Current calculation is the foundation of sizing; stay conservative and round up to the next standard frame instead of inventing a 22A part. Memorise a few example figures so site estimates beat the handbook, and review selections at a glance.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor ratings per GB/T 755; protective coordination per GB/T 14048 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.