Worked current calculations for main and control circuits

How much current does an 11kW motor draw, and what flows in a contactor coil loop? Without current numbers, sizing and protection are guesswork. This page works both sides through concrete examples with formulas and results.

1. How it works

Rated current of a three-phase motor follows I = P/(1.732 x U x cosphi x efficiency). For 11kW at 380V with cosphi 0.85 and efficiency 0.9, I = 11000/(1.732 x 380 x 0.85 x 0.9) which is about 21.8A; the shop rule of roughly 2A per kW gives 22A and confirms it. Feeder current for several motors sums the loads times a diversity factor of 0.7 to 0.9. From there set the breaker at 1.05 to 1.1 times rated current and the thermal relay at 0.95 to 1.05 times.

2. Numbers and practice

Control current has two parts: holding and pull-in. An AC110V auxiliary relay holds at about 0.03A (a few watts) and pulls in at 5 to 10 times that, around 0.2A; a large-frame contactor on AC220V holds at 0.1 to 0.5A with a several-fold inrush. Transformer sizing multiplies the sum of simultaneous holding powers by 1.5 to 2: six 3W relays plus two 20VA contactors at 0.8 diversity is roughly 40VA, and a 250VA unit leaves generous margin on top of lamps and PLC loads.

3. Pitfalls and fixes

Verify three things after calculating: conductor ampacity at least 1.2 times the computed current; secondary fusing at 1.5 to 2 times loop rating so pull-in shocks do not melt the fuse; and any measured deviation above 10 percent from calculated current deserves investigation rather than a quiet adjustment of settings. Do the arithmetic twice, once by formula and once mentally; a gap over 10 percent means a copied parameter.

4. Worked example figures

ItemFormulaResultUsed for
11kW motor rated current11000/(1.732x380x0.85x0.9)About 21.8ABreaker and cable sizing
Feeder composite current(11+5.5+2.2)kW x 2A x 0.8About 30ACommon feeder sizing
Contactor coil holding20VA/220VAbout 0.09ATransformer VA budget
Relay pull-in current0.03A x 8About 0.24AFuse withstand check
Transformer capacity(6x3+2x20)VA x 0.8 x 1.5About 62VA250VA fitted with margin
Secondary fuseLoop current x 1.5 to 2Rounded to sizeRide through inrush

5. Notes

Current calculation is the foundation of sizing; stay conservative and round up to the next standard frame instead of inventing a 22A part. Memorise a few example figures so site estimates beat the handbook, and review selections at a glance.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor ratings per GB/T 755; protective coordination per GB/T 14048 series. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Skipping power factor and efficiency in quick estimates undersizes cables for low-efficiency motors
② Counting only holding VA without margin lets simultaneous pull-in dip the voltage and chatter contacts
③ Fusing at holding current alone ages the element on every start and causes nuisance blowing months later

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.