Common interlock faults include no action, misoperation and simultaneous closing. This article gives a standard procedure from appearance, control voltage, contact continuity to loaded test, with corresponding repairs.
If pressing a button does not pull in the contactor, first check control supply voltage, blown fuse and start-button NO continuity, then the self-latch contact and coil. For interlock, confirm the opponent is not pulled in and its NC contact is truly closed; if the opponent is stuck energized it will lock this branch through the interlock.
Unexpected tripping or both closing usually means interlock failure: check whether the interlock contact is wrongly NO, omitted, or paralleled instead of series, and whether main contacts are welded causing short on switch. Measure interlock continuity with power off, and before energizing always disconnect the load and do a no-load operation to see mutual exclusion. Follow look-listen-ask-test: inspect burns, measure voltage and insulation, test contacts, then no-load interlock test; correct per schematic, replace stuck or welded parts, and finally redo the simultaneous-button test and loaded run.
| Fault | Cause | Action |
|---|---|---|
| No action | Low voltage or open | Check supply, continuity |
| Misoperation | Interlock wrong | Correct per drawing |
| Dual close | NC as NO | Return to NC |
| Frequent trip | Welded main | Replace contactor |
| Wrap-up | No-load interlock | Redo test |
Interlock fault troubleshooting must follow a systematic order of voltage, insulation, contacts and interlock test, not random parts swapping. Interlock errors mostly show as NC to NO, omitted or paralleled; after repair use simultaneous-button test and loaded run as closed-loop verification that the two are truly mutually exclusive.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear per GB 14048.4, insulation coordination per GB/T 16935.1, referencing IEC 60947 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.