In packaged switchgear (switchgear cubicle, distribution box) elements are packed tight, and the component designation is the lifeline that untangles hundreds of loops. Here is how codes are assigned and marked in packaged equipment.
Arrangement: split by function unit across cubicles and compartments, giving each a higher level code such as =A incoming, =B outgoing; give position codes inside the cubicle by mount location (plus C1 cubicle 1, plus C2 cubicle 2), then by row column within; use QF KM M on power, KA KT on control, HL on signal; drawers or modules keep their own code so pulling does not lose identity; with many loops in one cubicle link loop number and code (loop 1 KM is KM1).
Marking and wiring: tag each element with a durable code label, the door layout shows code plus position matching hardware; group terminal blocks by unit, terminal X1:1 maps to the loop; make secondary wire numbers carry code information such as 1KM1:13 meaning loop 1 KM1 terminal 13, so tracing locates at a glance; on inter cubicle wires mark source and target cubicle codes for clear trace; keep factory drawing and in cubicle labels on one revision and verify one by one at acceptance.
| Stage | Do | Use |
|---|---|---|
| Zone | Unit higher | =A=B |
| Locate | Position code | +C1 |
| Power | QF/KM/M | Clear |
| Secondary | Carry code | 1KM1:13 |
| Inter cub | Source target | Trace |
| Label | Durable | One rev check |
Rule: in packaged equipment split by function unit with higher level code (=A incoming, =B outgoing) and position code (+C1 cubicle); keep power QF/KM/M, control KA/KT, signal HL distinct; make secondary wire numbers carry the code (1KM1:13) for glance tracing, group terminals, mark source and target between cubicles, use durable labels, and verify drawing against hardware on one revision at acceptance.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Item codes per GB/T 5094 (IEC 61346), packaged switchgear per GB/T 7251 series, symbols per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.