Using the most typical two-motor sequential start, this article explains every component's role and current path. It builds the foundation: SB, KM main/aux contacts, thermal, interlock each do what, so a newcomer can wire a two-stage line alone.
Main circuit: two motors M1, M2 each via KM1, KM2 main contacts to supply, each with thermal FR1, FR2 and breaker. Control: SB1_1/SB2_1 for M1, SB1_2/SB2_2 for M2; KM1, KM2 coils; KM1 NO as M2 start-permit; KM1, KM2 NC for各自 stop and interlock.
Start (M1 then M2): press SB2_1, KM1 pulls in and self-holds, M1 runs; KM1 NO closes giving M2 start circuit power permit. Now press SB2_2, KM2 pulls in and holds, M2 runs. If SB2_2 is pressed first, KM1 NO is open so M2 coil has no path and M2 stays still - the circuit forces M1 first. This is the minimal runnable sequential model.
Stop and protection: press SB1_1 stops M1, KM1 drops, M1 stops and KM1 NO opens removing M2 permit (M2 already running keeps by its own hold unless SB1_2 pressed). Thermal FR tripping opens its NC to stop the coil for overload. FR1 trip stops only M1, FR2 only M2, no cross effect, clear layered protection.
| Device | Role | Motor | Note |
|---|---|---|---|
| KM1 | M1 main contactor | M1 | NO permits M2 |
| KM2 | M2 main | M2 | needs permit |
| SB2_1 | M1 start | M1 | with hold |
| SB2_2 | M2 start | M2 | permitted |
| FR1/FR2 | overload | each | thermal NC |
| SB1 | stop | each | interlock |
Rule: KM1 NO is M2 start permit, KM1 drop removes M2 permit, FR each its own. Newcomers identify components first then wire by the table; a two-stage sequence wires in one go.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Components per GB/T 4728, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.