Wrong star-delta wiring most often explodes at the switching moment, tripping the upstream breaker. This article lists three typical short-causing mistakes at the six terminals, the KM2 bridge and the interlock, then gives a step-by-step ohmmeter check to locate the fault safely.
Mislabeled six terminals can short the supply when delta closes. Before wiring, buzz out each U-V-W group with a continuity tester and compare with the nameplate diagram; never trust wire color alone because a wrong star point ties two phases together and shorts the source at switch.
A reversed KM2 bridge shorts two phases the instant delta closes, blowing contacts and tripping the breaker. Verify with an ohmmeter that like phases conduct only through the intended bridge, and confirm the interlock prevents KM2 and KM3 from pulling in together at any time during the transfer.
Missing interlock contacts let both contactors close at once, a direct phase-to-phase short. Always prove with indicator lamps that the two contactors never actuate simultaneously before applying power, then trial the switch live with the panel guard in place.
| Fault type | Symptom | Check point | Fix |
|---|---|---|---|
| Mislabeled terminals | contactor explodes at switch | buzz U-V-W groups | rewire per nameplate |
| Reversed bridge | breaker trips, sparking | ohm KM2 like-phase | correct bridge |
| Missing interlock | both close together | check NC series | add interlock |
| Loose star point | open-phase noise | tighten terminals | re-crimp |
| Wrong coil volts | chatter | measure coil | change coil |
Rule: confirm by buzzing before wiring, draw the bridge exactly, never omit the interlock. After any change, pre-check like-phase conduction and star-point continuity with an ohmmeter while de-energized, then power up only when clean and safe.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Wiring symbols per IEC 60617, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.