How a wiring diagram marks wire numbers decides whether a fitter can see at a glance where each wire goes. Inconsistent marking turns the drawing into a puzzle.
On a terminal wiring diagram every conductor carries a number, placed at or near the wire ends, usually beside the wire or above the terminal lead-out. GB/T 6988 requires a one-to-one wire-to-number match; the terminal-strip drawing shows the number beside each terminal lead-out, and the device side shows it at the element terminal. The number must equal the one on the schematic, never a second scheme.
Numbers are alphanumeric such as 101, W1, X1:3. A wire crossing pages shows both ends, e.g. 101 to 202-3 meaning page 202 point 3. Cores inside a multicore cable read cable-core like C1-2. Font is clear and unobscured, with a leader line if needed. Complex panels use source-plus-destination marking so either end can be traced back.
| Element | Marking | Requirement |
|---|---|---|
| Position | By wire / above term | One-to-one |
| Consistency | Same as schematic | No second set |
| Destination | Near + far page | Traceable |
| Core | Cable-core | e.g. C1-2 |
| Clarity | Font unhidden | Leader if needed |
| Complex | Source+dest | Both ways |
Rule: wiring-diagram numbers equal schematic numbers, placed by the wire or above the terminal, with full near and far ends (page or device point); multicore uses cable-core. Font clear and unobscured, complex panels marked both ways for reverse trace.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Wiring diagrams and documentation per GB/T 6988 series, graphical symbols per GB/T 4728, conductor marking per GB/T 7947. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.