After years of service screws loosen from vibration and heat cycles; a loose point heats past 100 degrees and burns the strip. This page covers periodic retightening, infrared scanning and check intervals.
Terminal screws relax under vibration and thermal cycling: retighten a new cabinet after three months in service (torque 0.5 to 1.2 N·m by size), then once a year, with power and high-current terminals as the priority, each driven to torque. Inspect visually at the same time: discolouration, baked or cracked bodies, damaged wire insulation. Record every retightening with cabinet, strip and date.
The maintenance workhorse is an infrared thermometer: scan the strip at load peak; a terminal over 20 degrees above ambient opens the cabinet for a close look, over 40 degrees means immediate isolation. Three hot-point causes: loose screw (poor clamp), thin wire (overload), small terminal (undersized). Fix by retightening, thicker wire or a bigger block. Scan twice a year and add a summer peak check, replace any discoloured terminal rather than polishing it, and keep a hot-spot log to swap whole strips that keep heating.
| Item | Method | Interval |
|---|---|---|
| Retighten | Torque driver | 3 mo + yearly |
| Scan | IR gun | Half year + summer |
| Visual | Colour crack | Each opening |
| Sleeves | Fallen moved | Each opening |
| Bridge | Loose | Yearly |
| Record | Log | Every time |
Retighten at three months and yearly to torque, scan with IR at load peak: over 20 degrees above ambient investigate, over 40 degrees isolate. Hot points mean loose screws, thin wire or undersized terminals, fixed by tightening, thicker wire or bigger blocks. Replace discoloured terminals, keep a hot-spot log and swap whole strips that repeat.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical maintenance per GB 50168, terminals per IEC 60947-7-1, safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.