Multiple motors like conveyor trains must start in fixed order or they jam and backflow. This article gives the design idea: use the front contactor auxiliary NO as the start-permit for the next, forming cascaded interlock, with the overall main and control frame.
Conveyors, pump sets and machine tools with several motors have a process order: the rear device must wait until the front runs normally, or material backflows and mechanics jam. Sequential start writes the rule no-front-no-rear into the circuit by electrical interlock, physically preventing wrong start; it is a hard process-safety requirement.
In design, place the front contactor (KM1) NO auxiliary in series with the rear (KM2) start circuit, so KM2 energizes only after KM1 pulls in; KM2 NO then feeds KM3, cascading stage by stage. Only front-to-back start is possible, and any stage stop opens the chain and drops the following stages, achieving linked protection.
Main circuit: each motor its own contactor and protection. Control: unified L1L2, each stage start button parallel with self-hold, stop button in series after the front interlock. Design with an interlock-relation table listing who permits whom, then wire from it; far steadier than thinking on the fly. Reserve emergency stop and fault indication for operation.
| Item | Do | Effect | Error |
|---|---|---|---|
| Interlock | front NO in rear | order only | miss series |
| Cascade | front to back | no backflow | reverse |
| Ctrl supply | unified L1L2 | common | wrong phase |
| Self/stop | hold+stop each | safe | no hold |
| E-stop | total stop front | all stop | no total |
| Lamps | run lamp each | clear | no lamp |
Rule: front NO in rear, cascade front to back, unified L1L2, self-hold and stop each, total E-stop at front. Design the interlock table first, then wire from it without chaos.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Design per GB/T 4728, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.