When a reversing circuit is converted to inverter control, the phase-swapping job moves entirely to the drive, and both wiring and protection must be rebuilt. This article covers the changes: a simplified main circuit, how forward-reverse commands enter, what happens to brake and limits, and which original components must stay.
The main circuit shrinks: the drive feeds from a breaker plus one isolating contactor, and its output goes straight to the motor. The crossed-phase KM2 and both reversing contactors disappear; motor leads land fixed, with rotation set by the drive. The thermal relay can go, since the electronic thermal protection takes over, but its parameters must match the motor rated current. Soft-start parts and the mechanical interlock kit retire.
Direction commands enter through the drive control terminals: FWD and REV digital inputs wired from the original button circuit, keeping the button interlock so both commands cannot be active together, with speed from a potentiometer or analog input. Control wiring uses shielded twisted pair routed away from power cables, shield earthed at one end. The latch logic simplifies: run commands go straight to the drive, and the run signal via an auxiliary relay drives the indicator. The emergency stop either drops the run command or cuts control power depending on the safety level. Components that stay: the input breaker or fuses for short-circuit duty, an input contactor for isolation, a separately controlled brake circuit, and the limit NC contacts wired into the respective direction command loops. Commission by auto-learning the motor data, jogging both directions no-load, checking accel and decel times against the inertia, and proving the limits cut the right command. Set the drive to pass through zero frequency on reversal to avoid a plug-reverse trip.
| Item | Mains, two contactors | Inverter control |
|---|---|---|
| Direction elements | KM1 KM2 crossed | FWD/REV terminals |
| Overload | Thermal relay | Electronic thermal |
| Reversal shock | Plug-reverse inrush | Smooth via zero Hz |
| Limits | NC in coil branch | NC in command loop |
| Brake | With main circuit | Independent circuit |
Inverter conversion is a whole-chain rebuild, not just swapping contactors for terminals: short-circuit protection, overload, reversal logic, limits and brake all need re-verification. With the two contactors gone, isolation and brake reliability matter even more; archive every drive parameter in the commissioning record.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 12668 series for adjustable-speed drives, GB/T 5226.1 for machinery safety, IEC 61800 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.