Design of Phase-failure Protection in Motor Control Circuits

When a three-phase motor loses one phase it runs single-phase with the other two phases at 1.7 to 2.4 times rated current, heating rapidly until the winding burns. This article explains how to design phase-failure protection that cuts power immediately on open phase.

1. How it works

Phase loss raises the remaining two phase currents to 1.7 to 2.4 times rated, drops torque and speed, and causes violent heating that destroys insulation within minutes. Many burned motors root in undetected phase loss, so standards mandate phase-failure protection, especially for unattended and continuous-duty machines. The protection must act to disconnect the supply without delay.

2. Practice and pitfalls

Thermal relays usually include phase-failure protection via a differential mechanism that opens the control circuit when one phase current vanishes, the common choice for fixed-frequency motors. Integrated protectors detect phase loss electronically and fast. Contactor-type schemes use an intermediate relay sensing three-phase voltage and dropping out on any loss. VFD drives detect and fault on phase loss. Design the protection to de-energise the contactor coil and coordinate with overload and short-circuit protection.

3. Phase-failure Design Table

MethodActionUse
ThermalDifferentialFixed-freq
ProtectorElectronicCritical
VoltageDrop-outContactor
VFDFault stopDriven
Neg-seqDetect negativeCritical

4. Notes

Phase-failure protection is key to prevent motor burn. On open phase the remaining currents reach 1.7 to 2.4 times rated. Use thermal relay with phase-loss or integrated protector, act to cut the contactor coil, and coordinate with overload and short-circuit. Test by simulated phase loss regularly.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor protection see GB/T 5226.1 (IEC 60204-1), low-voltage apparatus see GB/T 14048.5, machines see GB/T 755, phase-loss protection see relevant standard. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Fuse as phase-loss: other phases still overcurrent
② Thermal without phase-loss: no protection
③ Alarm only not cut: motor keeps burning

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL