Knowledge Base › Electrical Knowledge Base › PLC input and output modules: symbols, addressing and common terminals
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

PLC input and output modules: symbols, addressing and common terminals

PLC I/O modules are drawn as boxes with terminals carrying addresses. This page explains how input and output modules are drawn, how addresses are annotated so they match the ladder program, and how commons are handled.

1. How it works

In GB/T 4728 practice a PLC is a rectangular box for the CPU or rack, with I/O points drawn as small terminals inside carrying addresses such as I0.0 and Q0.1. Inputs face the signal source and outputs face the load. Drawings range from a single labelled box with the model number to a fully expanded terminal plan where every I/O point carries its sensor or actuator address. The addresses must match the ladder program exactly, otherwise the download scrambles which input drives which output.

2. Practice and pitfalls

The commons carry the traps: input commons COM connect to supply positive or negative depending on sink or source wiring; relay outputs have COM and NO terminals; transistor outputs split into source and sink types. Mark the COM of every output group and state clearly whether the module is NPN or PNP and relay or transistor. The input common wiring decides which sensor types work, and one wrong COM note blanks every input. Module supply and earth terminals are drawn too and bonded to protective earth.

3. PLC module symbol drawing table

SectionSymbolAnnotationCaution
CPU boxrectanglemodelsupply and earth
Input pointterminal II0.0common COM
Output pointterminal QQ0.1COM wiring
Relay outputcontact boxQ with COMAC and DC both fine
Transistor outputtransistor markQ source/sinkNPN or PNP marked

4. Notes

Draw PLC modules as boxes with terminals, and keep every address identical to the ladder program. The commons, NPN or PNP type and relay versus transistor output must all be stated, otherwise the download misroutes actions or nothing works at all. An I/O address table generated from the program beats hand copying every time.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: PLC symbols per GB/T 4728.12; systems per IEC 61131 and GB/T 15969 series. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Address table disagreeing with the program: after download the button does nothing and actions land on wrong outputs
② Output COM left unconnected: every output stays dead
③ PNP sensor wired to a sink input: the signal sits at one level for ever

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.