A timer set for ten seconds that runs thirteen knocks the whole cycle off beat. This page separates the three roots of timing error, device type, supply voltage and ageing, and gives a stopwatch-and-multimeter verification routine that brings the delay back inside tolerance.
Start by comparing the nameplate with the measurement. Air-damped timers carry an inherent error near plus or minus ten percent, so an eight percent reading is normal; electronic types sit near five percent and only exceed ten percent when something is wrong; digital types reach one percent. If the measured deviation stays inside the type allowance, compensate with the setting knob instead of replacing the unit. Mind the range: rotary timers are least accurate at the ends of their scale, so a ten-second target belongs on a 0 to 30s dial, not a 0 to 60s one.
Supply voltage is the overlooked variable. An electronic timer fed below eighty-five percent of rating starts to drift; one 220V unit measured at 180V stretched its delay by about seven percent. Air-damped types with a weak coil fail to complete the armature stroke and can miss by fifteen percent. Monitor the coil voltage with a multimeter during pickup; a pronounced dip points to an undersized control supply or excessive line drop, and a secondary winding that sits below ninety percent of rating must be fixed before the timer is touched. Coil heating raises resistance, which is why a marginal timer reads true in the morning and drifts by afternoon.
Verify in three moves: time five runs and average them, where scattered readings mean contact or mechanism bounce and steady readings mean systematic error; compensate the setting twice until the target is met; then run a heating test, comparing a cold measurement with one taken after ten consecutive cycles, and replace with an electronic type if the difference exceeds three percent.
| Symptom | Error magnitude | Likely cause | Action |
|---|---|---|---|
| Steady overshoot | 5%~10% | Inherent type error | Compensate setting, stay mid-range |
| Error follows voltage | Over 10% | Low or dipping control voltage | Check transformer secondary and line drop |
| Cold differs from hot | Over 3% | Coil heating shifts characteristics | Fit electronic type or improve ventilation |
| Large run-to-run scatter | Irregular | Worn mechanism or contact bounce | Listen at pickup, replace the unit |
| Drifts worse over months | Growing | Dust in chamber or ageing capacitor | Clean chamber or fit electronic type |
| Long delays badly off | Over 15% | Range chosen too large | Fit smaller range, set mid-scale |
Classify the symptom first and the detours disappear. The rules are compensate before replacing, power before timer, records before hands; once every timer has a measured archive on the cabinet door, correcting a setting becomes arithmetic rather than guesswork.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Timing accuracy and test methods refer to the GB/T 14598 series; control circuit voltage levels and tolerances follow GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.