Button interlock breaks first by mechanism, contactor interlock cuts by contact logic. Used together in forward-reverse circuits they form a double interlock with much higher safety. This article analyses the action sequence and benefits of the dual interlock.
A twin push button has mechanically linked NO and NC contacts: pressing forward first breaks the reverse NC then makes forward NO, blocking the reverse contactor at the button level. Its advantage is instant action without waiting for the opponent to release, but if the button sticks or wears the interlock fails, so button interlock alone is not reliable.
Contactor interlock series the opponent NC auxiliary in its own coil branch, cutting the opponent whenever the contactor physically pulls in, independent of button state, more reliable than button interlock. Combined, pressing a button first breaks the opponent by button, and once it releases its interlock contact resets so the other can pull in, forming double protection. Test both levels separately during commissioning.
| Method | Basis | Reliability |
|---|---|---|
| Button | Mechanical break | Affected by stick |
| Contactor | Logic cut | More reliable |
| Dual | Two levels | Highest safety |
| Failure | Single gap | Dual covers |
| Test | Verify each | Both required |
Button plus contactor interlock forms the standard safe double interlock for forward-reverse duty. The button compensates the contactor delay while the contactor compensates button sticking; commissioning must verify both levels are effective.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear per GB 14048.4, control circuit devices per GB 14048.5, machinery safety per GB/T 16855.1, referencing IEC 60947 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.