Wiring pushbuttons and indicator lamps in star-delta control

Buttons and lamps are the eyes and hands of the star-delta human interface. This article explains wiring start SB2 and stop SB1, and which auxiliary contacts feed the run, star and delta indicator lamps, so operators read status at a glance.

1. How it works

Stop SB1 is normally closed, wired first in the control supply so pressing it cuts all control. Start SB2 is normally open, parallel to the KM1 holding NO contact; pressing it bypasses the hold to pull KM1 in, then KM1 self-hold keeps it. SB2 across KM1 NO gives press-and-run, the most basic hold circuit, and the order must not reverse.

2. Numbers and practice

For lamps, the power lamp takes control L1L2 (lit means control live). Run lamp takes KM1 NO (lit when KM1 in). Star lamp takes KM3 NO (lit in star), delta lamp takes KM2 NO (lit in delta). The three-lamp combo reads: power only = standby, power plus star = starting, power plus delta = normal run, a clear status at a glance with fewer misreads.

3. Pitfalls and fixes

If the control is 380 V, use 380 V lamps or step down to 220/24 V; never put a 220 V lamp on 380 V. A fault lamp can take the thermal or phase-loss NC contact (lit normal, off or flashing on trip). All lamp negatives tie to N or the control common, wire de-energized, and lamp holders must be tight.

4. Star-delta button lamp wiring table

DeviceSignalMeaningWire
SB1 stopNC in ctrl heademergency off
SB2 startNO on KM1 holdpress-run
Power lampL1L2ctrl live
Run lampKM1 NOmain in
Star lampKM3 NOstar run
Delta lampKM2 NOdelta run
Fault lampthermal NCalarm

5. Notes

Rule: SB1 NC first, SB2 NO across self-hold; three lamps from KM1/KM3/KM2 NO for run/star/delta. Wire de-energized, match lamp voltage to control, and status becomes obvious with fewer misreads.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control devices per IEC 60947-5, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Use NO for stop button, never cuts.
② Lamp on wrong voltage, burns.
③ Wrong contact for lamps, status chaos.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.