Action sequence analysis of the three contactors

The pull-in and drop-out order of KM1, KM2 and KM3 decides whether start-up is smooth or explosive. This article walks through the contact states in four stages: power-on, star, switch and delta, and shows how the interlock contacts are wired.

1. How it works

Power-on stage: KM1 pulls in first and self-holds. Press SB2, KM1 energizes, three-phase reaches the motor via KM1 main contacts, and its NO auxiliary closes for self-hold (parallel to SB2) while its NC auxiliary opens to lock later logic. KM2 and KM3 are still open, motor has no power.

2. Numbers and practice

Star stage: KM3 pulls in and KT starts timing. After KM1, a branch feeds KT and KM3 coils; KM3 shorts U2V2W2 to a star point and the motor runs star at low voltage. KM3 NC auxiliary opens and deadlocks the KM2 coil so the delta contactor cannot pull in now.

3. Pitfalls and fixes

Switch stage: KT timed out acts its contact, first de-energizes KM3 (star point opens), after a few ms mechanical or electrical dead band energizes KM2. KM2 bridges the windings to delta. KM2 NC had already deadlocked KM3, giving interlock. Delta stage: KM1 and KM2 hold, KM3 stays released. Stop SB1 drops KM1 and KM2, motor coasts free. Dynamic braking needs a separate circuit; star-delta itself has no braking.

4. Three contactor action sequence

StageKM1KM2KM3
Power-onin, holdreleasedreleased
Starinreleasedin
Switchinbreak then makemake then break
Deltaininreleased
Stopreleasedreleasedreleased
Interlocklocks laterlocks KM3locks KM2

5. Notes

Rule: KM1 first, KM3 next, KT times, KM3 breaks before KM2 makes, KM2 holds. Not one interlock contact may be omitted or the switch shorts. Verify stage by stage with lamps in commissioning.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Sequence logic per GB/T 4728 symbols, safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Omitting KM2 KM3 interlock lets them close together and short the supply, NC interlocks must cross-series.
② Reversing KT contact type keeps KM3 in or KM2 out and scrambles timing, check the timed contact.
③ Omitting self-hold drops out on release and cannot run continuous, KM1 NO parallels the start button.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.