Where the strip sits decides how easy wiring is and how much noise enters: too high needs a stool, too low needs squatting, next to a heat source it bakes. This page covers height, zoning and clearance rules.
Mount for standing work: strip centre between 400 and 1600 mm above the cabinet bottom; over 1800 mm needs a stool and under 300 mm needs squatting. Keep at least 150 mm clear in front for hands and tools, never mount a part blocking the strip face, and keep strips off the door unless using hinge pass-through terminals.
Zone by function: incoming terminal strips near the bottom entry to shorten cable runs; signal strips near the PLC side; power strips near the power devices so mains wires do not cross the signal area. Keep away from heat sources (over 100 mm from transformers and starting resistors), away from below drive outputs (EMI), and away from dripping paths. Keep 30 mm behind the strip for wiring, draw the layout first, verify door operation and rear routing, then drill.
| Item | Rule | Reason |
|---|---|---|
| Height | 400-1600 mm | Standing work |
| Front | ≥150 mm | Tool access |
| Incoming | Bottom entry | Short runs |
| Heat | ≥100 mm away | No baking |
| Rear gap | ≥30 mm | Routing |
| Bend radius | ≥200 mm | Thick cable |
Mount strips 400 to 1600 mm high with 150 mm front space; incoming strips at the bottom, signal strips near the PLC, power strips near power devices, avoiding heat, drive outputs and drips with 30 mm rear routing space. Verify on the layout before drilling holes.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Assemblies per GB/T 7251.1, safety per GB/T 5226.1, documents per GB/T 6988. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.