Where to mount terminal blocks inside a cabinet

Where the strip sits decides how easy wiring is and how much noise enters: too high needs a stool, too low needs squatting, next to a heat source it bakes. This page covers height, zoning and clearance rules.

1. How it works

Mount for standing work: strip centre between 400 and 1600 mm above the cabinet bottom; over 1800 mm needs a stool and under 300 mm needs squatting. Keep at least 150 mm clear in front for hands and tools, never mount a part blocking the strip face, and keep strips off the door unless using hinge pass-through terminals.

2. Practice and pitfalls

Zone by function: incoming terminal strips near the bottom entry to shorten cable runs; signal strips near the PLC side; power strips near the power devices so mains wires do not cross the signal area. Keep away from heat sources (over 100 mm from transformers and starting resistors), away from below drive outputs (EMI), and away from dripping paths. Keep 30 mm behind the strip for wiring, draw the layout first, verify door operation and rear routing, then drill.

3. Mounting position requirements

ItemRuleReason
Height400-1600 mmStanding work
Front≥150 mmTool access
IncomingBottom entryShort runs
Heat≥100 mm awayNo baking
Rear gap≥30 mmRouting
Bend radius≥200 mmThick cable

4. Notes

Mount strips 400 to 1600 mm high with 150 mm front space; incoming strips at the bottom, signal strips near the PLC, power strips near power devices, avoiding heat, drive outputs and drips with 30 mm rear routing space. Verify on the layout before drilling holes.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Assemblies per GB/T 7251.1, safety per GB/T 5226.1, documents per GB/T 6988. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Strip mounted too high wastes time
② Parts blocking the strip face stop tools
③ Next to heat bakes terminals brittle

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.