When a motor must start and stop from two places, how does the latch wire. This page gives the standard multi-station latching connection.
Multi-station control follows one rule: all stop buttons (NC) are in series on the common feed, all start buttons (NO) are in parallel across the latch contact. Any stop cuts everything, any start builds the latch. Each station gets its own start-stop pair; stop is series, start is parallel, and the latch stays the KM auxiliary.
Wire: supply to SB1a (stop A, NC) to SB1b (stop B, NC) to [SB2a (start A, NO) parallel SB2b (start B, NO) parallel KM aux] to coil to N. Any stop opens the loop; any start energizes the coil, KM pulls and self-holds. Three or more stations extend the same way: stops all series, starts all parallel.
| Button | Wire | Role |
|---|---|---|
| Stop A | NC series | cut all |
| Stop B | NC series | cut all |
| Start A | NO par | latch |
| Start B | NO par | latch |
| Latch | KM aux | hold |
| Extend | add KA | long run |
For multi-station control put every stop in series and every start in parallel, with the KM auxiliary as the latch. Any station can stop or start. Use an intermediate relay for long runs, label wires per station, and test each station.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control circuit GB/T 5226.1 with IEC 60204-1; relay GB/T 14048. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.