Wrong earth terminal config means leakage protection fails and signals pick up noise. This page shows how to place earth terminals and keep protective and signal earth separate.
Earth terminals sit at both ends of the strip or on a separate row, marked green-yellow and labelled PE, never mixed with ordinary terminals in the same number range. Each cabinet needs at least one protective earth bar whose capacity is not less than the incoming PE, with noisy devices like VFDs and servos grounded separately to it. Trap: bolting equipment chassis to an ordinary terminal means a loose connection leaves the frame live undetected.
Keep protective earth (PE and signal earth (SE) separate and joined only at one point to true earth. Signal earth uses its own thin green-yellow bar; shield braids ground at one end only to avoid ground loops. Analogue and comms grounds float or isolate and must never tie to PE to form a big circulating current. Draw a clear grounding sketch and measure each point under 4 ohm at acceptance.
| Item | Require | Note |
|---|---|---|
| Position | Ends/sep | Green PE |
| Protect | Own bar | ≥Incoming |
| Signal | Separate | One point |
| Shield | One end | No loop |
| Spare | 20% | For retro |
| Resist | ≤4Ω | Test |
Place earth terminals at strip ends or a separate row, green-yellow PE, not mixed with ordinary. Keep PE and signal earth apart, single-point to true earth, shield one-end grounded. Cabinet bolt at least M8 to plant earth, leave 20 percent spare earth terminals, measure under 4 ohm, never crimp earth on ordinary terminals.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation per GB/T 6988, earthing per GB/T 50054, marking per GB/T 4026, assemblies per GB/T 7251.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.