Old gear is relay wiring, new gear is PLC; how do the two drawings correspond? This page maps relay schematics to ladder logic.
In the relay schematic one coil (e.g. KM1) maps to one PLC output point (Q0.0); buttons, limits and relay contacts map to inputs (I0.0) or internal flags (M). The ladder diagram moves the physical relay logic into a scan cycle: each network is one logic rung from left to right bus. Knowing this mapping lets you rewrite a relay schematic as a PLC program.
Difference: relays act in real parallel (contact closes, action instant); PLC scans every tens of ms, a lag you can ignore. A self-hold in the schematic is a parallel normally-open contact; in ladder it is the output contact paralleled before the condition. Trap: one relay contact appearing in several loops must reuse the same M bit in ladder; interlocks use the other side normally-closed in both.
| Schematic | Ladder | Note |
|---|---|---|
| Coil KM | Output Q | 1 to 1 |
| Button SB | Input I | NO/NC |
| Contact | Flag M | Reuse |
| Self-hold | Output par. | Same |
| Interlock | Series NC | Same |
Relay coils map to outputs, buttons and contacts to inputs or flags; the ladder moves physical logic into the scan cycle. Self-hold parallels NO and interlock series NC, same in both. Build a map table and monitor bits online then trace to the physical state. Keep both drawings with PLC addresses on the schematic.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Documents per GB/T 6988, PLC systems per IEC 61131-3. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.