Common terminal strip faults and remedies

Strip faults look varied but fall into a few classes: contact-resistance heating, short circuits, insulation decay and marking errors. This page walks cause and remedy by symptom with a fast locating method.

1. How it works

Heating faults: the terminal discolours, smells burnt, the IR gun finds a hot spot. Nine cases in ten are poor contact: loose screw, stranded wire without a lug shedding strands, or mismatched wire and terminal. De-energise and re-crimp: fresh lug, torque to spec, change the block if the section mismatches, and check the neighbours on the same strip for the same batch fault. Badly burnt blocks go whole; burnt wire ends are cut back and re-stripped.

2. Practice and pitfalls

Short-circuit faults: the breaker trips on power-up, sometimes smoke. Usual causes: exposed copper bridging neighbours (over-stripping), metal swarf in the gaps, a jumper across the wrong holes. Isolate, measure resistance between adjacent holes hole by hole to find the short, clean and re-crimp. Insulation decay shows as low earth insulation and leakage alarms: dust and moisture in the gaps or cracked bodies. Clean, dry, fit dust covers, replace cracked blocks and retest at 500 V megger over 1 megohm. Log every fix with symptom, cause and remedy.

3. Fault quick reference

SymptomUsual causeFix
Heat colourLoose or no lugRecrimp torque
Trip on powerExposed copper swarfClean restrip
Low insulationDust moisture crackClean replace
OpenBroken coreTrace by number
False alarmMarked wrongCheck drawing
Strip repeatsBatch assemblySwap strip

4. Notes

Heat means poor contact: recrimp to torque and swap burnt blocks whole. Shorts: clean swarf and restrip exposed copper. Low insulation: clean, cover and retest at 500 V megger over 1 megohm. Locate by look then measure: buzzer along the wire for opens, adjacent-hole resistance for shorts, and log every fix in a fault ledger.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical maintenance per GB 50168, terminals per IEC 60947-7-1, assemblies per GB/T 7251.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Swapping one block without checking the strip repeats
② Skipping the insulation retest leaves a hazard
③ Not cutting burnt wire ends keeps bad contact

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.