Knowledge Base › Electrical Knowledge Base › Timer-based delayed reversal in forward-reverse circuits
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Timer-based delayed reversal in forward-reverse circuits

Direct live reversal hammers the drive; timer-based delayed reversal is the classic remedy. This article covers the design: how the timer inserts into the reverse branch, choosing between off-delay and on-delay, how to set the delay time, and reference values for typical machines, giving smooth and efficient changeover.

1. How it works

The design point is to route the reverse start through a timed contact: pressing reverse first breaks the forward path so KM1 drops, while the timer KT coil energizes; only after the set delay does the KT timed NO contact close and pick up KM2, so reverse start is forcibly postponed until the motor has stopped. A KT instantaneous NC contact belongs in the forward branch as interlock, preventing a false forward start during the waiting window, and KT must reset reliably when de-energized.

2. Practice and pitfalls

Set the delay by motor size and load inertia: small motors with light loads need only half a second to one second; above ten kilowatts or with high inertia, two to five seconds. Time the coast-down of the motor with a stopwatch and set the delay to about 1.2 times that, long enough to protect, short enough to keep the operator happy. An on-delay closing contact in series with the reverse branch is the clearest arrangement; take care not to swap the instantaneous and timed contacts. Typical applications include winches, planer tables and large-inertia fans. Commission no-load first: pressing reverse must drop KM1 at once, start the timer, and pick KM2 only at the end, with no overlap; measure the real delay and reset if it deviates more than twenty percent. Watch the reduced inrush and listen to the gearbox under load. Air-bellows timers drift with age, so prefer electronic types or re-check periodically.

3. Delay setting reference for timed reversal

Motor powerLoad typeReference delay
Below 5.5 kWLight fans and pumps0.5 to 1 s
7.5 to 22 kWMedium inertia1 to 2 s
Above 30 kWHigh inertia2 to 5 s
WinchPotential-energy loadBrake first, then delay
VerificationStopwatch on siteWithin 20 percent

4. Notes

Delayed reversal trades half a second of waiting for the removal of a tenfold inrush, multiplying contact life. Calibrate the setting on site, re-check drifting bellows timers, and never omit the KT instantaneous interlock, or both directions gain an energizing window during the wait.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 and GB 14048.5 for apparatus, GB/T 5226.1 for machinery safety, IEC 60947-5-1 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Delay set too short: the inrush remains and contacts still erode
② KT instantaneous interlock omitted: false-start risk during the wait
③ Bellows timer drift unchecked: protection loses its timing

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.