The schematic shows logic, the wiring diagram shows the real box; mismatch between them is the worst trap. This page maps the latch circuit across both drawings.
The schematic draws connections and logic by function; one device like KM appears split across loops (main, coil, aux) all marked KM to show linkage. The wiring diagram draws physical position, terminal numbers and every wire end to end. The schematic tells why it conducts, the wiring diagram tells how to connect.
On the schematic: supply to SB1 NC to SB2 NO parallel KM aux to KM coil to N, and power to QF to KM main to FR to M. On the wiring diagram these become terminal numbers: SB1 1-2, SB2 3-4, coil A1-A2, aux 13-14, QF and FR ends, motor U-V-W, with wire numbers 1, 3, 5, U1 matching. Drawing not matching the box is the biggest hazard.
| Item | Schematic | Wiring |
|---|---|---|
| KM | split | term no |
| Latch | par SB2 | 13-14 |
| Stop | NC ser | 1-2 |
| Wire no | logic | real |
| Match | must | on door |
| Pit | type wrong | copy no |
The schematic splits a device by logic with one symbol; the wiring diagram shows terminals and wire numbers. Walk each schematic branch along current, swap symbols for terminals and number the wires to get the wiring diagram. Keep drawing and box identical, post the diagram on the door, and confirm the latch point 13-14 is NO.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drawing per GB/T 6988, symbols GB/T 4728 with IEC 60617. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.