Wrong cable marking on the drawing leads to wrong wiring on site. This article explains how to mark wire numbers, cross-section and core count of wires and cables in circuit diagrams per standard so anyone can wire correctly.
Wires are numbered by equipotential principle: wires at the same potential share a number. Main circuits use digits (1, 2, 3 phases and N, PE), control circuits use segmented odd numbers (1, 3, 5 and so on) to distinguish branches. Marking includes wire number, conductor cross-section and core count, for example 3 times 1.5 or BVR-3 times 2.5. Multi-core cables show total cores and purpose such as 7 times 1.0 control. Wire numbers match terminal blocks one to one; change drawing and wiring diagram together.
Cables are shown by thick or special line with model, size, start and end such as YJV-4 times 2.5 from distribution to motor. Terminal blocks follow numbering like X1:1, X1:2 consistent with the wiring diagram, each terminal marked with wire number and destination. Shielded cables show the shield earth symbol, armoured cables show earth. State colour by text or code (green-yellow PE, phase sequence). Marking must be uniform and unambiguous for wiring and tracing.
| Object | Mark | Basis |
|---|---|---|
| Wire | No+size | Equipotential |
| Cable | Model+end | Wiring |
| Terminal | Block+pt | Consistent |
| Shield | Earth sym | Stated |
| Colour | Code | Prevent |
Mark cables by equipotential number, full size and core count, cable model with start and end, terminal number matching the wiring diagram, and state shield earth. Never skip equipotential numbering, size, cable ends or shield earth; put uniform marking into the drawing template.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical drawings see GB/T 6988, graphical symbols see GB/T 4728, letter symbols see GB/T 7159, conductors see GB/T 3956, safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.