Signal lamp and indicator light symbols with their colour meanings

An indicator lamp is a circle with an X inside, and the colour carries a fixed meaning. This page explains the standard drawing of indicator lamps and the colour code of GB/T 4025 that keeps operators reading the right message.

1. How it works

An indicator lamp (HL) is drawn as a circle containing a crossed X or a lamp outline. It is a signalling device with no contacts of its own; external contacts light it. The X represents the filament, and some drawings add small rays outside the circle. Lamps get serial codes HL1, HL2 and so on. Do not confuse it with an illuminated push button, where the button and the lamp are combined into one symbol.

2. Practice and pitfalls

Per GB/T 4025 the colours carry fixed meanings: red for danger, emergency and stop; yellow for caution and abnormal warning; green for safety, running and start permitted; blue for a mandatory action such as reset required; white for general information with no special meaning. The drawing does not colour the symbol, so the material list or the lamp label must state the colour, and a red lamp drawn where the panel logic expects green leaves the operator reading a running machine as healthy while it has failed.

3. Signal lamp colour meaning table

ColourMeaningTypical useCode
Reddanger and stopemergency, faultHL red
Yellowcaution, warningoil temperature highHL yellow
Greensafe, runningnormal startHL green
Bluemandatory actionreset requiredHL blue
Whitegeneral informationpower onHL white

4. Notes

The circle with an X inside represents the filament, and the colour follows the fixed meanings of GB/T 4025 with colour and meaning recorded in the material list. A wrong colour misleads the operator about machine state, and a signal lamp must never be drawn as a push button symbol.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Indicator lamp symbols per GB/T 4728.7; colour meanings per GB/T 4025 and IEC 60073. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Red lamp installed as green: operator reads a fault as normal running
② All lamps white with no distinction: nobody can tell which circuit failed
③ Signal lamp drawn as a push button: it gets operated as one by mistake

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL