Jog means run only while held, so after a blackout the motor should stay still, yet some jog loops spin up when power returns, a hidden danger. This page covers the cause of abnormal auto-start and how to handle it.
Pure jog needs a human holding the button to close the control loop, so on restore with nobody pressing, the loop is open and the motor stays still. There is no self-recovery in a proper jog. If the motor auto-starts on return, the loop has picked up a latch or stray conduction: a wrongly paralleled KM auxiliary, a button wired NC, a PLC holding output, or welded main contacts.
Causes: a stray self-hold that closes on restored supply; an NC button that is live at power on; a PLC retentive output that restores; welded main contacts that keep the motor energized even with control off; or an UPS-fed control supply with a bad button state. Any of these turns jog into a dangerous auto-start.
| Symptom | Cause | Fix |
|---|---|---|
| Spin on return | stray hold | remove |
| Live at on | NC button | use NO |
| PLC starts | retentive | non-ret |
| Still live | welded | swap |
| Rule | no auto | manual |
| Protect | UV trip | enforce |
A standard jog will not self-start after blackout; if it does, the loop has gained a latch, an NC button, a PLC holding output or welded contacts. Remove stray holds, use NO buttons, use non-retentive PLC bits, check for weld, add undervoltage or power-on inhibit. Critical machines must never auto-start, require manual reset.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machine electrical safety GB/T 5226.1 with IEC 60204-1 forbids hazardous auto-restart. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.