Motors burn because protection is incomplete or settings are arbitrary. This page explains which protections a motor needs and how to calculate each setting so the motor survives overloads and faults.
Every motor needs at least short-circuit protection (fuse or breaker instantaneous), overload protection (thermal relay or electronic protector) and phase-failure protection (built into the thermal or separate). Larger or critical machines add earth-fault, locked-rotor and undervoltage protection. VFD-driven motors rely mainly on drive-internal protection with an upstream breaker as short-circuit backup. Configure in tiers: the upstream breaker handles shorts, the downstream thermal handles overload, neither fighting the other.
Set overload protection at 1.0 to 1.2 times the motor rated current so it holds at rated load and trips on inverse time under overload. Set breaker instantaneous at 8 to 12 times rated, clearing the 5 to 7 times starting current without nuisance trip. Phase-failure protection acts when any phase current collapses. Earth-fault protection uses residual current, 30 mA for personal protection and several hundred mA for fire protection. Settings must match the nameplate and starting method, and frequent starters need a starting-shock-resistant type.
Typical errors: thermal set too low trips on every start or short overload and stops the line; too high and a real overload never acts until the winding burns. Breaker instantaneous too small trips at start; too large and a short is cleared too late. Ordinary fuses used as motor short-circuit protection blow on starting inrush. Adding a thermal relay to a VFD motor is wrong because it measures power-frequency current. Set by nameplate, tier the protection, keep margin, and verify by loaded test trip.
| Protection | Device | Setting |
|---|---|---|
| Overload | Thermal relay | (1.0~1.2)In |
| Short | Breaker inst | 8~12x |
| Phase loss | Thermal/sep | On loss |
| Earth | RCD | 30mA~hundreds |
| Locked rotor | Protector | By multiple |
Motor protection works by tiers and nameplate-based settings: overload at 1.0 to 1.2 times rated, short-circuit at 8 to 12 times trip, phase loss and earth fault added per risk. VFD motors use drive-internal protection with a breaker backup, and every configuration ends with a loaded test trip.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor protection see GB/T 5226.1 (IEC 60204-1), low-voltage apparatus see GB/T 14048.5, machines see GB/T 755. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.