Multi-point control in crane operation

A crane needs start-stop and e-stop from cab, floor and remote, the classic battlefield of multi-point control. This note covers how to lay it out, how e-stop series-wires a double chain, and how inching and speed change parallel, against GB 6067.

1. How it works

A crane has at least cab, floor pendant and wireless remote, sometimes a maintenance platform. All start and inch buttons parallel, all stop and e-stop series back to the main contactor and each mechanism contactor. Cab and floor stop chains are series together, so any e-stop releases the main contactor and kills all power. Control voltage is usually 36 V safety extra-low voltage per GB 6067 and GB/T 5226.1 to prevent shock.

2. Practice and pitfalls

Safety hinges on e-stop and zero position. Each e-stop is series in the main stop chain and mechanically linked to the main contactor, pressed it must cut main power. Zero-position protection requires each controller at zero before start, preventing sudden motion on power restore; its contact also series in the start branch so any handle off zero cannot start. Inching buttons parallel across the hold for non-latching, speed buttons switch resistance or drive gear. All e-stops stay hard-wired series even on wireless, safety never relying on the signal. Acceptance tests every point start-stop and every e-stop cutting main power.

3. Crane multi-point sheet

PointControlSafetyStandard
CabStart speedE-stop mainGB 6067
FloorStart e-stopIn chainGB/T 5226.1
RemoteCommandWired stopSELV
ZeroZero protectIn startNo false
Voltage36V SELVAnti shockGB 6067
AcceptPer pointCut mainSign

4. Notes

The core of crane multi-point control is any point cutting main power in emergency, e-stop hard series, zero protection in start, 36 V safety voltage. Wireless e-stop stays wired, safety independent of signal. Accept per point and per e-stop cutting main.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Crane safety per GB 6067, control per GB/T 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① E-stop not main: no cut
② No zero protect: sudden move
③ Wireless e-stop: uncut loss

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.