Knowledge Base › Electrical Knowledge Base › Drawing order of the star-delta reduced-voltage control schematic
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Drawing order of the star-delta reduced-voltage control schematic

A correct star-delta schematic is the premise of correct wiring. This article gives the standard drawing order from the main circuit through KM1, KM3 star point and KM2 bridge to the control circuit with KT and interlocks, noting GB/T 4728 symbols.

1. How it works

Start the main circuit from the three-phase supply L1L2L3: KM1 main contacts feed motor starts U1V1W1; KM3 contacts short U2V2W2 to a star point; KM2 contacts form the bridge linking U2-W1, V2-U1, W2-V1. Draw these three branches clearly with solid lines, the bridge exactly, as the base of the whole drawing.

2. Numbers and practice

Then draw the control circuit taking L1L2: SB1 stop, SB2 start, KM1 self-hold, then the KT coil (energized via KM1 NO) and its delayed changeover contact, NC in KM3 coil and NO in KM2 coil. Add the KM2/KM3 NC interlocks in series; lay the control out left-to-right, supply on top, load below, with clear interlock routing.

3. Pitfalls and fixes

Mark every device with standard GB/T 4728 symbols; contactors, timers, buttons and thermals each have a prescribed form. Label terminals U1U2V1V2W1W2 correctly and distinguish multiple contacts of one device by letter. Put a title block and drawing number at top-right, add notes where complex, and self-check the bridge and interlocks before issuing the drawing.

4. Star-delta schematic drawing order

StepDrawKeyEasy error
1 main powerL1L2L3 to KM1supply firstorder reversed
2 star pointKM3 shorts U2V2W2solid lineloose
3 bridgeKM2 links U2W1 etcthree pairsreversed
4 ctrl powertake L1L2not L1L3cross
5 KT interlockdelay contact plus NCbreak-makereversed
6 labelingGB/T 4728 symstandardmissing

5. Notes

Rule: main circuit in three layers (supply, KM1, star/bridge), control in five steps (start-stop, self-hold, KT, interlock, label). After drawing, check the bridge and interlocks line by line against the real device; a right drawing enables right wiring and saves rework.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Schematics per GB/T 4728, design per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Draw bridge from memory, shorts on switch.
② Omit interlock line, both pull in.
③ Ignore GB/T 4728 symbols, miswire.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.