One wrong character between the sleeve and the drawing means a wrong wire on site. This page covers marking principles, keeping drawing and hardware in step, and the consistency check routine.
Four principles: uniqueness, one number points to one wire in the cabinet, duplicates are fixed immediately; consistency, drawing, sleeve and wire table agree character for character including case and separators; both-ends, the same wire carries the same number at each end; readability, letters outward, uniform direction, legible size. On drawings the number sits beside the wire, cross-page wires are marked at both pages, and wires either side of a jumper keep their own numbers.
Consistency comes from process, not goodwill: print the wire table after drawing approval, sleeve by table during cabling, spot-check 10 to 20 percent at acceptance, and change the drawing before the wire on retrofit, fitting new sleeves the same day. Version control: a drawing revision forces a wire-table check and the two must ship at the same version. Trap: the drawing changed but the sleeves did not (or the reverse), so the next service is wrong either way; and multiple fitters printing in different formats makes one cabinet look like two shops.
| Check | What | How |
|---|---|---|
| Uniqueness | Duplicates | Table scan |
| Consistency | Three places | Char by char |
| Both ends | Same number | Look both |
| Readability | Direction face | Visual |
| Spot | 10-20% | QC |
| Version | Same revision | Check tags |
Follow the four principles: unique, consistent across drawing, sleeve and table, same at both ends, readable. Enforce by process: sleeve by table, 10 to 20 percent spot checks, drawing first on retrofit with sleeves changed same day, and drawing plus table at one revision. Laminate the table on the door and fix mismatches on the spot.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Documents per GB/T 6988, marking per GB/T 4026, wires per IEC 61175. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.