Control wire too thin overheats and roasts insulation, too thick wastes money and is hard to terminate. This page explains the current-carrying and voltage-drop method so the calculation is never wrong.
Choose cross-section first by continuous ampacity: consult the wiring ampacity table. Control circuits carry a few amperes and commonly use 1.0 to 1.5 mm square copper; main circuits follow the motor rated current, about 1.5 mm square for 10 A and 10 mm square for 50 A. Ampacity drops with installation: conduit cuts roughly 20 to 30 percent, and bundling reduces further; above 40 degree ambient derate. The rule is the conductor never exceeds its insulation temperature class, 70 or 90 degree, otherwise the insulation cooks.
Long runs need a voltage-drop check: control circuits usually allow 5 to 10 percent drop or the remote contactor lacks pull-in force. Drop equals current times length times resistance, with copper resistance about 0.0172 ohm mm square per metre. For a 24 V control circuit running 30 m at 2 A, 1.5 mm square drops about 0.69 V or 3 percent and passes, while 0.75 mm square exceeds 5 percent. Remote or low-voltage circuits therefore need larger sections.
Common mistakes: using 1.5 mm square everywhere without checking, so remote contactors never pull in; ignoring voltage drop because ampacity suffices, leaving control voltage at the critical edge; no derating for multiple conductors in one conduit, overheating in summer; running signal and power cables in the same conduit, causing interference and nuisance action. Do it right: select by ampacity, verify by drop, enlarge for long runs, separate strong and weak cables. Short cabinet jumps can follow ampacity alone, but field long runs must check drop.
| Current | Copper size | Note |
|---|---|---|
| Up to 6 A | 1.0 mm sq | Control wire |
| Up to 10 A | 1.5 mm sq | Common |
| Up to 20 A | 2.5 mm sq | Derate in conduit |
| Up to 30 A | 4 mm sq | Derate |
| Up to 50 A | 10 mm sq | Main circuit |
Select conductor cross-section by ampacity first and voltage drop second; 1.0 to 1.5 mm square covers control wiring and main circuits follow the motor current. Never use one size everywhere without checking drop on long runs, derate in conduit and keep signal and power separate, or remote contactors fail to pull in.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Conductors see GB/T 3956, low-voltage equipment see GB/T 5226.1 (IEC 60204-1), wiring see GB/T 16895 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.