Knowledge Base › Electrical Knowledge Base › Common faults and handling of star-delta control circuits
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Common faults and handling of star-delta control circuits

Star-delta faults cluster into three types: no start, switch failure, and open-phase overheating. This article gives a cause tree and handling steps for each, covering buttons, coils, contacts, thermal relays and the timer, with a quick-reference table.

1. How it works

No reaction when pressing start usually points to the control circuit. First measure 220V at L1L2 from the control transformer, then check whether stop button SB1 is stuck or start button SB2 is oxidized. If supply and buttons are fine, measure the KM1 coil resistance for burnout and check the KM1 holding contact for a cold solder joint; most no-starts are lost control power or a bad button.

2. Numbers and practice

Starts but never switches to delta means the timer or KM3 loop fails. Check that KT is energized and timing; a worn pneumatic diaphragm may not act while an electronic one may have a wrong set value. A reversed KT contact keeps KM2 from pulling in, and a missing KM3 NC interlock can lock KM2 out entirely.

3. Pitfalls and fixes

Open-phase overheating in run comes from burnt main contacts. De-energized, test KM1 and KM2 main contacts; replace pitted pairs. If the thermal relay trips early, check its setting at 0.577Ie and replace an aged bimetal strip, since open-phase current rises fast and can burn the winding.

4. Star-delta common fault table

SymptomLikely causeCheckFix
No startno control powermeasure L1L2check button coil
No switchKT failswatch KT lampreplace KT
Both closeinterlock missedcheck NCadd interlock
Open phaseburnt contacttest contactswap pair
Thermal tripswrong settingread settingreset replace

5. Notes

Rule: no start checks control power and button, no switch checks KT and interlock, open-phase checks main contacts and thermal. Always de-energize and prove dead before measuring; use one hand and insulated tools on live control checks.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Device protection per IEC 60947-5, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Never probe contacts with bare hands live.
② Never set thermal at full Ie on star side.
③ Never swap a single contact alone.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.