Using off-delay time relay in control circuits

After stop the fan or oil pump must keep running a few seconds before cutting; only an off-delay relay handles this post-power delay. This note covers the wiring, use in cooling and pressure hold, and coordination with on-delay, so the machine no longer runs dry after stop.

1. How it works

The off-delay KT coil normally picked, its delay contacts act at once, say a delay-open NO contact closed supplying power. Once control supply loses, coil releases, contact starts timing and opens at set point. So the fan or pump is fed by this delay-open contact, after stop it stays closed a while, equipment keeps turning, auto cut at time. Key: KT coil must connect to a normally live supply not affected by stop, or take from main contactor auxiliary, ensuring correct energise duration.

2. Practice and pitfalls

Use one cooling fan: after main motor stops, fan fed by off-delay contact continues 10 to 30 seconds to carry heat away then stop, preventing burn on stop. Use two lube pump: after stop pump delays a few seconds to lubricate the last travel, prevent dry wear. Use three holding valve: after power valve coil held a few seconds then releases, completing a cycle. These three all need action to continue after de-energise. A system often uses both on-delay and off-delay: on-delay waits speed at start, off-delay waits cooling at stop. The two types must not mix; reversed, fan will not turn at start and runs wild at stop. Mark KT type and direction on diagram, accept with stopwatch: on energise measure delay close, on de-energise measure delay open, confirm both direction and value.

3. Off-delay use sheet

UseContactDurationPurpose
Cool fanDelay-open10-30sHeat
Lube pumpDelay-open3-10sNo dry
Hold valveDelay-open2-5sCycle
CoilLive srcTimingNo mix
CoordTypes clearDir rightAccept
AcceptStopwatchDir valSign

4. Notes

Off-delay KT times after de-energise then opens, for post-stop continuation: cooling fan 10 to 30 s heat, lube 3 to 10 s no dry, hold valve 2 to 5 s cycle. Coil on live supply for timing, with on-delay mark type direction on diagram, stopwatch confirm no reverse.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Off-delay and cooling per GB/T 5226.1 and GB 755, IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Coil wrong src: timing
② Mix on-off: fan reverse
③ No dir measure: reverse

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.