How to set aside spare terminals on a strip

When retrofitting, no spare terminals means tearing the strip apart, a bitter lesson. This page covers how many spares to leave and how.

1. How it works

Reserve about 10 to 20 percent of total terminals: 15 percent for small gear, 10 percent for big lines. Scatter them at each group end or as interleaved holes, not all piled at the strip end. Spares carry no wire but are marked spare with a reserved number so they are not misused. Trap: leaving none means a full strip swap when retrofitting.

2. Practice and pitfalls

On the drawing draw spare positions and mark spare with continuous numbering (X1:21 spare); fit blank terminals or end caps on the real strip to keep dust out. Reserve two or three at each group end and write the spare count into the order so the maker ships the gaps. On retrofit, check the count, enable a spare and update the drawing, or add a strip if short.

3. Spare terminal setup

ItemRuleWrong
Ratio10-20%None hard
SpreadGroup endNo pile
MarkSpareMisuse
RealBlank capShort
EnableChangeRecord
CountEnough?Add

4. Notes

Reserve 10 to 20 percent of terminals scattered at group ends with reserved numbers marked spare, and fit blank caps on the real strip. On retrofit check the count first, enable a spare and update the drawing, or add a strip if short. Log any borrowed spare and record every enable with a change order.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation per GB/T 6988, terminal marking per GB/T 4026. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① No spare: nowhere to add on mod
② Borrowed spare unlogged: misjudge
③ Real blank unmarked: thought used

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.