Jog and continuous run differ by only one wire: a latch contact across the start button. This page contrasts the two wirings so you see at a glance which wire was added.
A jog circuit has only a normally open button SB in series before the coil: press to run, release to stop. A continuous (latch) circuit adds a normally open auxiliary contact KM of the contactor in parallel across the start button SB2; once started the contact closes and bypasses the button so the motor keeps running after release. The difference is exactly that parallel wire.
On the drawing, jog is one series branch SB to KM coil to N. Continuous adds a normally closed stop button SB1 in series and a parallel KM auxiliary (marked 13-14 or 21-22) across SB2. So continuous needs one more stop button and one parallel latch wire. Converting jog to continuous is just adding that parallel contact and a stop button; mistake it as a normally closed aux and it latches at power on.
| Item | Jog | Continuous |
|---|---|---|
| Start | NO button | NO SB2 |
| Stop | optional | NC SB1 needed |
| Latch | none | KM NO aux |
| Release | motor stops | motor runs |
| Parallel | none | KM across SB2 |
| Use | setting | continuous |
Tell jog from continuous by the latch wire. For continuous run add the KM auxiliary NO contact, for pure jog remove it. Combined jog-continuous uses a selector or composite button; always check the contact type when wiring.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control design follows GB/T 5226.1 with IEC 60204-1; devices follow JIS C 4501. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.